Ningbo Xingbang Electric Co., Ltd.
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
It is specially designed for boundary spring operation mechanism and circuit breaker;
With wholly industrial design, it can adapt to severe outside environment;
Set functions of data acquisition, current protection, reclosing, wireless remote control, local control, state information acquisition and communication as one;
Relay controls output, available for any operating power;
Adopt LCD display and whole numeric keys, more convenient for operation;
Adopt fault wave-recorded, convenient for fault analysis;
Adopt aviation socket to connect to circuit breaker, convenient for installation and maintenance.
Brief:
XB821 user boundary switch controller is a control equipment specially designed for outdoor medium voltage circuit breakers. When inter-phase short circuit and single-phase earth fault occur in users branch, boundary circuit breaker immidiately open and insulate faulty line, so as to recover other branches power supply.
XB811 reclosing controller can help circuit breakers to realize data acquisition and telemetry, current protection, reclosing, faults recording, remote communication, local/remote control operation, and switch state acquisition /output, etc.
Performance parameter:
Environment: Temperature: -40℃~70℃;Relative humidity: 10%~100%;
Rating data: Rated voltage: 220V/100V; Rated current: 1A, 5A; Frequency: 50Hz;
Wattage consumption: In non-communication, active power≤5W, apparent power≤10VA;
Sampling precision:DC sampling precision: grade 0.5; Power precision: level 1;
Electro Magnetic Compatibility: Fast transient disturbance test, high frequency disturbance test, surge test, electrostatic discharge test,and radiation electromagnetic interference test to the device all can meet the requirement of DL/T721-2000 Distribution Automation System Terminal Unit;
Insulation test: Insulation test is accord with the demand of GB/T14598.3-93 6.0;
Impulse voltage test is accord with the demand of GB/T14598.3-93 8.0
Main Functions:
1,Telemetry
Three-phase voltage,three-phase current, P,Q,S,CosΦ;
Zero-sequencevoltage, zero-sequence current;
Frequency;
Voltage harmonic, current harmonic;
2,Telesignalisation
4-line telesignalisation acquisition;
Switch position signal(closing position, opening position);
Energy stored signal;
Operating button state (closing, opening );
3,Function of control
Support circuit breaker to switch through operation panel;
Support circuit breaker to switch through hand-held wireless remote controller;
Support circuit breaker to switch through wireless terminal PDA;
Support remote master station to realize circuit breaker's switching.
4,Current protection
Quick break, flash quick-break, three-phase overcurrent protection;
Inverse current-limiting protection;
Zero-note current protection and small current grounding protection.
5,Reclosure
0~3 times automatically reclose;
Accelerate after reclosing.
6,Switching management and blocking control
Power-on closing;
Non-voltage opening;
7,Maintenance
Setting protection parameter through local dial switches;
Support searching date and setting parameter and constant value through short-range wireless communication PDA;
Support searching date and setting parameter and constant value through debugging local interface RS232.
8,Data storage
Can save curve data;
Can store voltage, current, power, and so on;
Record and store SOE(Sequence Of Event);
Save control and operating events;
Fault records and storage;
Support historical data added uploading.
9,Function of fault records
Can record and search current waveform of pre- and post-fault.
10,Communication Function
Support remote communication modes, such as GPRS/CDMA, etc.
Support DL/T634.5101-2002, DL/T634.5104-2002, GSM messages and many other communication protocols.
Installation size: